Calculators › Motor Sizing

Motor Sizing Calculation

Motor circuits use four different numbers for four different jobs — and the trap is using the nameplate where you should use the table, or mixing up the percentages. This is core SP-PH territory (HVAC = motors). Here's the whole sequence.

The rules at a glance (Article 430)

Conductor (430.22)125% of the table FLC
Overload (430.32)125% of nameplate FLA (SF ≥ 1.15 or rise ≤ 40°C); else 115%
Short-circuit/ground-fault (Table 430.52)Inverse-time breaker 250%, time-delay fuse 175%, nontime-delay fuse 300%
Disconnect (430.110)At least 115% of FLC
Key distinction (430.6): use the table FLC (430.248/430.250) for the conductor and short-circuit protection; use the nameplate FLA only for the overload.

Example 1 — 5 HP, 230 V, single-phase, SF 1.15

  1. Table FLC (430.248): 5 HP @ 230V single-phase = 28 A.
  2. Branch-circuit conductor (430.22): 125% × 28 = 35 A.
    1.25 × 28 A = 35 A → need a conductor rated ≥ 35 A 10 AWG Cu (75°C) = 35 A → use 10 AWG Cu
  3. Overload (430.32(A)(1), SF 1.15): 125% of nameplate FLA. If nameplate = 28 A:
    1.25 × 28 A = 35 A max overload
  4. Short-circuit/ground-fault (Table 430.52, inverse-time breaker 250%):
    2.50 × 28 A = 70 A → 70 A breaker (a standard size)
    If 70 A won't let it start, 430.52 allows going up (next size, then up to 400% for an inverse-time breaker).
  5. Disconnect (430.110): 115% × 28 = 32.2 A → choose a disconnect rated ≥ 32.2 A (e.g., a 60 A safety switch).

Example 2 — 10 HP, 460 V, three-phase

  1. Table FLC (430.250): 10 HP @ 460V three-phase = 14 A.
  2. Conductor (430.22): 1.25 × 14 = 17.5 A → 14 AWG Cu (75°C = 20 A) satisfies it; many shops use 12 AWG minimum by preference.
  3. Short-circuit (inverse-time breaker 250%): 2.50 × 14 = 35 A breaker (standard).
  4. Disconnect (430.110): 1.15 × 14 = 16.1 A → rated ≥ 16.1 A.
Note: the motor small-conductor exception means 240.4(D) does NOT cap these motor conductors
Exam tip: always read whether the motor is single-phase (Table 430.248) or three-phase (Table 430.250), and which voltage column. Picking the wrong table is the #1 motor mistake.
← Box Fill Next: Dwelling Load Calc →